The newly redesigned IMR 1050X Combustion System Analyzer eliminates the number one hassle for combustion contractors; the annual replacement and calibration of the O2 sensor. By replacing the electro chemical O2 sensor with the EOS Technology™ CO2 sensor, the IMR 1050X now takes direct CO2 measurements and calculates the O2 level. This lowers the cost of ownership by doing away with the annual replacements of the O2 sensor and reducing calibration drifting typically found with standard electro-chemical sensors. The EOS Technology sensor has an unmatched industry leading life expectancy of 10 years!
Temperature Measurement | 1050X | 1050X-NO |
---|---|---|
Flue Temp Range Inlet Temperature (probe – T2) Inlet Temperature (ambient) Flue (T1, Inlet T2 & _T) Accuracy |
20~2400°F (-29~1315°C) 20~2400°F (-29~1315°C) 32~112°F (0~50°C) |
|
Gas Measurement | 1050X | 1050X-NO |
Oxygen | 0~21%** | 0~21%** |
O2 resolution / accuracy | 0.1% / ±0.3% | 0.1% / ±0.3% |
Carbon Monoxide (CO) | 0~2000 ppm (4000 max 15 min)* | |
CO resolution / accuracy | 1ppm / ±10ppm < 100ppm ±5% rdg > 100ppm |
|
Carbon Dioxide (CO2) | 0~20% | 0~20% |
CO2 Resolution / accuracy | 0.1% / ±2% | 0.1% / ±2% |
Efficiency** | 0~99.9%** | 0~99.9%** |
Efficiency resolution / accuracy | 0.1% / ±3% | 0.1% / ±3% |
Excess Air** | 0~250% | 0~250% |
Excess Air resolution / accuracy | 0.1% / ±3% | 0.1% / ±3% |
CO / CO2 ratio** | 0~0.999 | 0~0.999 |
CO / CO2 resolution / accuracy | 0.001 / ±5% rdg | 0.001 / ±5% rdg |
Nitric Oxide (NO1) | – | 0~100 ppm |
NO1 resolution / accuracy | – | ±5 ppm < 100 ppm |
Pressure (Differential) | Range | Accuracy |
±0.08” wc (±0.2mBar) ±0.4” wc (±1mBar) ±32” wc (±80mBar) |
±0.002” wc (±0.005mBar) ±0.01” wc (±0.03mBar) ±3% rdg |
|
Pressure Resolution | 0.001” wc < 9.999” wg 0.01” wc < 10.0” wg 0.001 mBar < 24.999 mBar 0.01 mBar > 25 mBar |
* Measured at STP (standard temperature and pressure)
** Calculated value
1050X | O2, CO2, CO, draft, Condensation Trap, Flue Probe Particle Filter, Hard Case, Batteries, Quick Start Guide Owner’s Manual |
---|---|
1050X‐NO | O2, CO2, CO, NO, draft, Condensation Trap, Flue Probe, Particle Filter, Hard Case, Batteries, Quick Start Guide Owner’s Manual |
1050X KIT | 1050X Analyzer, Flue Probe, IR Printer, (2) K‐Type Temp Probes, (2) Static Pressure Hoses (1) True Draft Probe, Gas Tap and Hose, AC Adapter/Charger, Hard Case, (2) Printer paper rolls, (2) Particle filters, Batteries, Quick Start Guide, & Owner’s Manual |
1050X‐NO KIT | 1050X‐NO Analyzer Flue Probe, IR Printer, (2) K‐Type Temp Probes, (2) Static Pressure Hoses, (1) True Draft Probe, Gas Tap and Hose, AC Adapter/Charger, Hard Case, (2) Printer paper rolls, (2) Particle filters, Batteries, Quick Start Guide, & Owner’s Manual |
Allows for live fire / real time analysis and trouble shooting, while verifying and documenting needed adjustments, repairs or replacements.
The IMR 1050X allows the technician to simultaneously set gas pressure while doing a combustion test. Which allows for live fire viewing of combustion gases (over / under fire) while viewing and setting gas pressure to manufacture suggested specifications.
The auxiliary screen allows the tech to choose from an assortment of HVAC test parameters they want to view while performing various HVAC applications. This screen also allows a variety of test to be done simultaneously.
“Understanding the problem to extend practical solution is something what we have experienced. Their analysis & solution helped Dalmia Cement save recurring energy cost & efficiency in the process to improve quality of our material”
– Dalmia Cements Limited
“Chandak Instruments Pvt. Ltd., Nagpur’s services were utilized to do field study on our combustion air flow measurement. Their systematic approach on the entire process is well appreciated, based on the study carried out we could fine tune the flow meters installed & improve the overall process”
Tata Steel Limited, West Bengal
1050X KIT |
---|
1050X-NO KIT |